100mm VIDEO-GRAPHICS RECORDER: ISOLATED TRANSMITTER POWER SUPPLY USER WIRING (Cont.) Long terminal cover Isolated transmitter power supply Models 5100e / 5100V Recorder rear terminal panel Red Black Red Black R Red I V+ V- Black Transmitter Power Supply PCB Channel input INTRODUCTION User terminal block + - + + The circuit board is protected by a 20mm anti-surge (type T) fuse, the value of which depends on the supply voltage as shown in the table below. Other transmitters Transmitter R (minimum spec) = 1.4W, + This option consists of a circuit board, teminal block and suitable wiring inside a long terminal cover at the rear of the recorder. The board supplies three mutually isolated dc supplies (nominal 25 Volts) each of which is intended to power a single 0 to 20mA or 4 to 20 mA current loop. Access to the output wiring and to the fuse is achieved by isolating the recorder from mains power and opening the terminal cover (after removing its securing screw). The process is fully described below. Only one channel shown, for clarity. 1%. 100 or 250 as required (see table) 100 0V 0 mA 4 mA 0.4 V 20 mA 2.0 V 250 0V 1.0 V 5.0V Supply voltage 110V ac 120V ac 220V ac 240V ac Voltages generated by various currents for R = 100 and R =250 Figure 5 Application wiring Fuse rating 100 mA 100 mA 63 mA 63mA Part Number CH050012 CH050012 CH050630 CH050630 SPECIFICATION Physical The long terminal cover adds 71 mm (closed) or 186 mm (open) to the back-of-panel length of the recorder, as shown below. Otherwise the recorder dimensions are as given in the recorder user guide. 25mm (0.99 in) 284 mm (11.18 in) 213mm (8.39in) 137mm (5.4in) View on right hand side Mounting slot (Left hand side) Panel thickness (25.4mm (1 in) max) Safety Isolation Isolation (dc to 65Hz; BS EN61010) Channel to channel: Channel to ground: EUROTHERM LIMITED Faraday Close, Durrington, Worthing, West Sussex, BN13 3PL Telephone: 01903 695888. Facsimile: 01903 695666 e-mail: info@eurotherm.co.uk Website: http://www.eurotherm.co.uk Page 4 HA027489/1 (CN13088) Installation category II; Pollution degree 2. Installation category II 100V RMS or dc (double insulation). The rated impulse voltage for equipment on 100V RMS or dc (basic insulation). nominal 230V ac mains is 2500V. Pollution degree 2 Normally, only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation shall be expected. HA027489 Issue 1 Jly 01 Page 1 100mm VIDEO-GRAPHICS RECORDER: ISOLATED TRANSMITTER POWER SUPPLY ACCESS TO THE USER CONNECTIONS/FUSE USER WIRING Figure 4 shows the terminal block pinout, and figure 5 shows typical applications wiring. 1 2 3 Isolate the recorder from the supply voltage. At the rear of the recorder remove the terminal cover securing screw (figure 1), taking care to retain it for use in re-assembly. Open the cover to reveal the circuit board, user connections etc. (figure 2) Power cord to recorder USER CONNECTIONS O/P1 O/P2 O/P3 + + + Cable clamp Cover securing screw Fuse Figure 1 Retaining screw location Figure 2 Inside the terminal cover 4 The fuse is located as shown in figure 2. User wiring to the terminal block (figures 4 and 5) can be carried out now, or the terminal cover can be removed for convenience, as described in steps 5 onwards below. 5. Unplug the IEC connector from the rear of the recorder connector panel 6. Remove the cable clamp, retaining the fixings for later re-assembly. 7. Close the terminal cover, and lift it off, as indicated in figure 3. Recorder Body Figure 4 Terminal block wiring Terminal cover View on right hand side of recorder Lift off Figure 3 Lift terminal cover off its hinge. Page 2 HA027489 Issue 1 Jly 01 HA027489 Issue 1 Jly 01 Page 3