100mm VIDEO-GRAPHICS RECORDER: ISOLATED TRANSMITTER POWER SUPPLY
USER WIRING (Cont.)
Long terminal cover
Isolated transmitter power supply
Models 5100e / 5100V
Recorder rear
terminal panel
Red
Black
Red
Black
R
Red
I
V+ V-
Black
Transmitter Power Supply
PCB
Channel input
INTRODUCTION
User terminal block
+
-
+
+
The circuit board is protected by a 20mm anti-surge (type T) fuse, the value of which depends on the supply voltage
as shown in the table below.
Other transmitters
Transmitter
R (minimum spec) = 1.4W,
+
This option consists of a circuit board, teminal block and suitable wiring inside a long terminal cover at the rear of the
recorder. The board supplies three mutually isolated dc supplies (nominal 25 Volts) each of which is intended to
power a single 0 to 20mA or 4 to 20 mA current loop.
Access to the output wiring and to the fuse is achieved by isolating the recorder from mains power and opening the
terminal cover (after removing its securing screw). The process is fully described below.
Only one channel
shown, for clarity.
1%. 100
or 250
as required (see table)
100
0V
0 mA
4 mA 0.4 V
20 mA 2.0 V
250
0V
1.0 V
5.0V
Supply voltage
110V ac
120V ac
220V ac
240V ac
Voltages generated by
various currents for
R = 100 and R =250
Figure 5 Application wiring
Fuse rating
100 mA
100 mA
63 mA
63mA
Part Number
CH050012
CH050012
CH050630
CH050630
SPECIFICATION
Physical
The long terminal cover adds 71 mm (closed) or 186 mm (open) to the back-of-panel length of the recorder, as shown below. Otherwise the recorder dimensions are as given in the recorder user guide.
25mm
(0.99 in)
284 mm (11.18 in)
213mm (8.39in)
137mm
(5.4in)
View on right hand
side
Mounting slot
(Left hand side)
Panel thickness
(25.4mm (1 in) max)
Safety Isolation
Isolation (dc to 65Hz; BS EN61010)
Channel to channel:
Channel to ground:
EUROTHERM LIMITED
Faraday Close, Durrington, Worthing, West Sussex, BN13 3PL
Telephone: 01903 695888. Facsimile: 01903 695666
e-mail: info@eurotherm.co.uk
Website: http://www.eurotherm.co.uk
Page 4
HA027489/1 (CN13088)
Installation category II; Pollution degree 2.
Installation category II
100V RMS or dc (double insulation).
The rated impulse voltage for equipment on
100V RMS or dc (basic insulation).
nominal 230V ac mains is 2500V.
Pollution degree 2
Normally, only non-conductive pollution occurs.
Occasionally, however, a temporary conductivity
caused by condensation shall be expected.
HA027489
Issue 1 Jly 01
Page 1
100mm VIDEO-GRAPHICS RECORDER: ISOLATED TRANSMITTER POWER SUPPLY
ACCESS TO THE USER CONNECTIONS/FUSE
USER WIRING
Figure 4 shows the terminal block pinout, and figure 5 shows typical applications wiring.
1
2
3
Isolate the recorder from the supply voltage.
At the rear of the recorder remove the terminal cover securing screw (figure 1), taking care to retain it for use in
re-assembly.
Open the cover to reveal the circuit board, user connections etc. (figure 2)
Power cord
to recorder
USER CONNECTIONS
O/P1 O/P2
O/P3
+
+
+
Cable clamp
Cover securing
screw
Fuse
Figure 1 Retaining screw location
Figure 2 Inside the terminal cover
4
The fuse is located as shown in figure 2. User wiring to the terminal block (figures 4 and 5) can be carried out
now, or the terminal cover can be removed for convenience, as described in steps 5 onwards below.
5. Unplug the IEC connector from the rear of the recorder connector panel
6. Remove the cable clamp, retaining the fixings for later re-assembly.
7. Close the terminal cover, and lift it off, as indicated in figure 3.
Recorder
Body
Figure 4 Terminal block wiring
Terminal
cover
View on right hand
side of recorder
Lift off
Figure 3 Lift terminal cover off its hinge.
Page 2
HA027489
Issue 1 Jly 01