IAQ Check List

advertisement
IAQ Check List
Building: Isaac Fox Elementary School
Date: October 21, 2011
IAQ Check List
Building Inspection Performed by: Lyle Erstad, Denys Armashov
Report Compiled by: Lyle Erstad
Check List
True False
N/A
1. Ground Level Indoor Inspection
a. Univents are on and air discharge grills are free of obstructions.
If false, send email to building principal and facilities director asking staff to be instructed to keep vents
clear at all times. Record locations here:
2. Ground Level Outdoor Inspection (weather permitting)
a. Univent air intakes are free of obstructions.
If false, record locations here:
b. Filters
i. Medium efficiency filters are installed in all univents.
If false, list locations and create work orders to initiate corrective action.
ii. High efficiency filters are installed in the air handling units.
If false, list locations and create work orders to initiate correction action.
iii. Filters are being changed every six months and the installed date is written on the outer filter casing.
If filter is older than 6 months, list locations and create work orders to initiate corrective action.
c. Insects, bird nests, or droppings are not evident near outdoor air intakes.
If false, indicate locations here:
d. Trash dumpsters are located away from doors, windows, and outdoor air intakes.
e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial
plants, exhaust from nearby buildings)
f. Trucks and buses are not allowed to keep their engines idling near the building.
Page 1 of 9
Revised 3/7/2011 AMJ
Created 11/2010
IAQ Check List
IAQ Check List
Building: Isaac Fox Elementary School
Date: October 21, 2011
Building Inspection Performed by: Lyle Erstad, Denys Armashov
Report Compiled by: Lyle Erstad
Check List
True False
g. No evidence of drainage problems exist. Water drains away from the building including roof
downspouts.
N/A
h. Sprinklers do not spray directly toward the building or into outdoor air intakes.
i.
j.
Grass clippings from mowers are directed away from the building air intakes.
The landscaper has been informed to blow clippings away from the building. This is being
monitored.
Clean walk-off mats are present at exterior entrances.
3. Roof (Inspections conducted weather permitting)
a. Roofing consultant has not found any issues requiring immediate repair.
Most recent roofing inspection date/company: 5-year roofing plan completed 5/25/2010 with C. E.
Crowley & Associates. Over the summer and early Fall we accomplished an aggressive maintenance
plan for district roofs. Also each roof was thermally scanned which identified areas of wet
insulation. There were three (3) areas identified at Isaac Fox. The wet insulation was cut out and
removed and the roof repaired. Also, during the building inspection for this report, a roof drain
was identified as having an active leak. It is above the ceiling in the custodial storage room near the
office. A plumbing contractor has been called to assess and repair.
b. There is no evidence of water ponding on the roof.
This is a ballasted roof but no evidence of ponding was apparent.
c. Intake ventilation units are operating properly and free of debris.
These were all cleaned over the summer.
d. All exhaust fans are operating properly and free of debris.
e. Air intake dampers are set to allow air flow even at minimum setting.
f. Insects, birds, animal nests or droppings are not evident near outdoor air intakes.
Page 2 of 9
Revised 3/7/2011 AMJ
Created 11/2010
IAQ Check List
Building: Isaac Fox Elementary School
Date: October 21, 2011
IAQ Check List
Building Inspection Performed by: Lyle Erstad, Denys Armashov
Report Compiled by: Lyle Erstad
Check List
True False
g. Plumbing stacks and exhaust vents are located away from air intakes.
N/A
4. Attic
a. There is no evidence of roof or plumbing leaks.
No Attic
b. There is no evidence in attic of insects, birds, animals, or nests.
No Attic
5. General Considerations
a. Classrooms, offices and/or common areas appear recently cleaned.
If examples of poor housekeeping are found, record locations below:
b. Only vacuums with HEPA filters are being used.
c. All supply and exhaust ventilation units are working properly.
d. Occupied space temperatures and relative humidity levels are within the standards listed below.
i. Temperature range:
Winter temperatures 70-73 degrees.
Summer temperatures 74-80 in air-conditioned spaces and 74-85 in non-air-conditioned
spaces.
Outdoor air temperature: 53.3; 55.3 degrees.
Highest temperature – Location: 102; 405; Reading of 75; 69.8 degrees.
Lowest temperature – Location: 314; 9; Reading of 69; 63.8 degrees.
ii. Relative humidity range is 30% to 60%.
Non-air-conditioned spaces may be higher on rainy or humid summer humid days.
All spaces may be less than 30% when the out-door air temperature is less than 32 degrees.
Outdoor relative humidity: 52.1; 28.1%
Page 3 of 9
Revised 3/7/2011 AMJ
Created 11/2010
IAQ Check List
IAQ Check List
Building: Isaac Fox Elementary School
Date: October 21, 2011
Building Inspection Performed by: Lyle Erstad, Denys Armashov
Report Compiled by: Lyle Erstad
Check List
True False
Highest relative humidity – Location: 315; 9; Reading of 49.9; 41.6%
Lowest relative humidity – Location: 107; 405;Reading of 31.9; 35.5%
N/A
Readings not within acceptable standards will result in the creation of a work order, requesting
maintenance to address. (Readings are noted on the attached test data sheet)
e. Occupied space readings of carbon monoxide (CO) levels are less than 9.0 PPM.
Outdoor Air CO Reading: 0; 1.3
Highest CO Location: 316; All Reading: .2; 0
Lowest CO Location: Several rooms
Reading: 0.0
If the CO level is greater than 9.0 PPM in any space as measured with a handheld device or “leave-in”
monitor, the space must be cleared of all occupants and steps taken to correct the problem. The issue
will be immediately addressed by maintenance and the Fire Department. (Readings are noted on the
attached test data sheet)
f. CO2 levels in any occupied space are below threshold limits.
i. Perform CO2 check with Gray Wolf or other portable device. Measure four times yearly or more
often if needed. Measure only in fully occupied rooms. Reading should be less than 700 PPM plus
outside air CO2 PPM.
700 PPM + 420; 409 PPM = 1120; 1109 PPM
Assume outside CO2 is 350 if temperature is below 41 degrees and air is not stagnant with no- wind.
Record all occupied space CO2 levels on forms provided. Provide the outdoor CO2 level as well as
the high and low CO2 extremes below:
Outdoor reading: 420; 409 PPM
Highest CO2 reading – Location: 312; 405; Reading of 1008; 670 PPM
Lowest CO2 reading – Location: 107; 9; Reading of 550; 663 PPM
Page 4 of 9
Revised 3/7/2011 AMJ
Created 11/2010
IAQ Check List
Building: Isaac Fox Elementary School
Date: October 21, 2011
IAQ Check List
Building Inspection Performed by: Lyle Erstad, Denys Armashov
Report Compiled by: Lyle Erstad
Check List
True False
N/A
ii. If reading is above threshold, check univent and air handling dampers to ensure a value is set to
provide at least 15 cfm of fresh air intake per student based on average space occupancies. If
reading is consistently elevated, then use data logging to monitor CO2 concentrations over time and
look for other sources of problems.
iii. CO2 levels were checked three months ago.
iv. CO2 levels on “leave-in” devices, where present, where checked.
NONE
g. Offensive odors are not apparent.
If false, list problem areas:
h. Water damage is not evident.
Check for roof leaks, pipe leaks, spills, stained ceiling tiles, etc, visually and with moisture meter. Look
for the source of any water leaks and schedule repairs. Discard porous items such as ceiling tiles if wet
for more than 24 hours. For carpeting, if less than 9 square feet of wet area, shampoo with germicide
and fan dry. For areas greater than 9 square feet, replace carpet with tile in reasonable timeframe. If
carpet is over ACM tile, replace during next unoccupied break time (winter break, spring break,
summer).
If false, record findings and locations here: There were stained ceiling tile in 9 and the custodial
storage room. Work orders were written to check out and then replace the tile. The custodial
Page 5 of 9
Revised 3/7/2011 AMJ
Created 11/2010
IAQ Check List
IAQ Check List
Building: Isaac Fox Elementary School
Date: October 21, 2011
Building Inspection Performed by: Lyle Erstad, Denys Armashov
Report Compiled by: Lyle Erstad
Check List
True False
storage room was from a leaking drain. Room 9 was an old roof leak.
N/A
i.
Mold or mildew growth is not evident.
If false, record findings and locations here:
j. All pest management issues are being handled by Integrated Pest Management.
We are in process of covering air intake vents with smaller mesh to keep out mice.
k. No other unresolved concerns or complaints by building personnel are known.
If false, list any pending issues not previously mentioned in this report here:
l. There are no incomplete HVAC preventative maintenance (PM) work requests.
If false, list any incomplete HVAC work request here:
6. Bathrooms and General Plumbing
a. All locker or restroom exhaust fans are working.
Inoperable or malfunctioning fans are listed as follows:
Location:
Problem:
b. All of the following drain-trap maintenance procedures are being conducted according to the frequency
indicated.
If false, indicate all deviations and locations:
i. Water is poured into floor drains once per week (approximately 1 quart of water) or water and a
teaspoon of cooking oil poured into the drain once a month.
ii. Water is poured into sinks at least once per week (about 2 cups of water).
iii. Toilets are flushed at least once per week.
7. Lab Chemicals & Maintenance Supplies
a. Lab chemicals are used with exhaust fans turned on.
Page 6 of 9
Revised 3/7/2011 AMJ
Created 11/2010
IAQ Check List
IAQ Check List
Building: Isaac Fox Elementary School
Date: October 21, 2011
Building Inspection Performed by: Lyle Erstad, Denys Armashov
Report Compiled by: Lyle Erstad
Check List
True False
b. Lab chemical storage areas have been inspected yearly by ROE and Fire Department.
Record last inspection dates below:
ROE: 10/10
LZFD: 10/10
N/A
c. Flammables are not stored with igniters.
d. All chemicals that may react or produce toxic or explosive by-products are separated and maintained in
approved containers stored in approved storage. (e.g. lockable, with appropriate ventilation).
e. Chemical disposal records for all lab chemicals are available for review.
f. All cleaning products used in building contain no/low VOC.
List any exceptions:
g. Increased ventilation is considered when installing new carpets, cleaning upholstered furniture,
shampooing carpets, etc.
h. Exhaust ventilation systems in chemical and trash storage areas are turned on and functioning properly.
i.
Portable fuel containers are properly closed.
j.
Power equipment, like snow blowers and lawn mowers, have been serviced and maintained according to
manufacturers’ guidelines.
k. Oil based paints are stored in approved storage cabinets.
No oil based paint is allowed in the district.
l. Green Cleaning products and processes are used in this building.
Page 7 of 9
Revised 3/7/2011 AMJ
Created 11/2010
IAQ Check List
Building: Isaac Fox Elementary School
Date: October 21, 2011
8.
IAQ Check List
Building Inspection Performed by: Lyle Erstad, Denys Armashov
Report Compiled by: Lyle Erstad
Check List
True False
N/A
Combustion Appliances
a. Combustion analysis is performed at the start of the heating season on all boilers. Adjustments are
made to the burners to correct any abnormalities and improve efficiency.
Combustion analysis is scheduled for Nov. 2 and 3 with Barr Mechanical.
b. In rooms that contain combustion appliances, there is no evidence of combustion gas or fuel odors.
If false, record locations here:
c. No leaks, disconnections, and/or deterioration were found on exhaust hoods.
d. Flue components are clean and free of soot.
e. All combustion appliances have flues or exhaust hoods and vent NO2.
i. If false, inspect cooking hoods, chemical hoods. Assure that cooking stoves and appliances are
correctly installed, used, and maintained according to manufacturers’ specifications.
ii. If not vented, ensure that “leave-in” CO monitors are placed in room. Record locations here: NONE
iii. CO levels in rooms with combustion appliances are measured and recorded with an IAQ monitor. CO
readings outside of normal CO range will result in an immediate response by maintenance to reduce
CO level or vacating the room/building, if necessary.
Record locations here:
9. Other
a. Paint
No peeling and/or flaking paint found.
If planned building renovation will damage paint or if peeling paint is discovered, lead testing may be
necessary. If peeling paint is found, send email to the building Principal and the Facilities Director
alerting them of the problem. Staff and teachers need to pick up any flakes of paint to prevent
children from being exposed. The Facilities Director will advise the Facilities Coordinator (a Certified
Lead Paint Renovator) to test the paint for lead. Lead paint was discontinued in 1978. Buildings built
Page 8 of 9
Revised 3/7/2011 AMJ
Created 11/2010
IAQ Check List
IAQ Check List
Building: Isaac Fox Elementary School
Date: October 21, 2011
Building Inspection Performed by: Lyle Erstad, Denys Armashov
Report Compiled by: Lyle Erstad
Check List
True False
after 1978 are exempt from lead paint testing.
N/A
If lead is present, required repairs should be done immediately using lead-safe methods and, if
necessary, a licensed lead contractor.
Location(s) of known peeling paint in building:
b. The following preventive measures are being taken to reduce lead exposure.
i. Play areas and toys are cleaned nightly.
Only play areas are cleaned by the custodians.
ii. Floors are mopped nightly.
iii. Dust at least weekly.
c. Radon testing is recommended by IEMA every 5 years. Last testing date listed below:
Date: 4/2009; Reading of <.5
d. The IAQ testing equipment used for this inspection was calibrated and is in good working order.
Equipment Used: Gray Wolf
Last date of calibration: 2-4-11
Page 9 of 9
Revised 3/7/2011 AMJ
Created 11/2010
Issac Fox Elementary 395 W.Cuba Road. IAQ Readings Fall 2011
Temperature °F
Relative Humidity
%RH
Carbon
Monoxide ppm
Carbon
Dioxide ppm
14-Oct-11 11:21:45 AM
53.3
52.1
0.0
420
14-Oct-11 02:14:18 PM
74.0
35.6
0.0
626
13
107
14-Oct-11 12:03:19 PM
71.3
31.9
0.0
550
24
Issac Fox Elementary
109
14-Oct-11 12:08:34 PM
72.9
38.9
0.0
688
101
Issac Fox Elementary
110
14-Oct-11 12:05:14 PM
73.0
39.5
0.0
653
11
Issac Fox Elementary
112
14-Oct-11 02:23:48 PM
72.7
37.3
0.0
679
18
Issac Fox Elementary
202
14-Oct-11 11:51:29 AM
74.1
38.1
0.1
741
3
Issac Fox Elementary
202A
14-Oct-11 12:21:05 PM
73.7
35.4
0.1
695
1
Issac Fox Elementary
203
14-Oct-11 02:08:19 PM
72.6
40.4
0.0
700
23
Issac Fox Elementary
204
14-Oct-11 12:23:20 PM
73.9
37.3
0.0
656
4
Issac Fox Elementary
205
14-Oct-11 12:24:29 PM
73.4
39.6
0.0
773
19
Issac Fox Elementary
207
14-Oct-11 12:25:47 PM
73.1
40.2
0.0
819
11
Issac Fox Elementary
208
14-Oct-11 12:28:59 PM
73.4
37.4
0.0
688
8
Issac Fox Elementary
209
14-Oct-11 12:30:11 PM
72.8
38.6
0.1
727
21
Issac Fox Elementary
210
14-Oct-11 12:31:35 PM
74.0
41.0
0.0
855
16
Issac Fox Elementary
300
14-Oct-11 11:44:23 AM
73.7
41.4
0.0
751
19
Issac Fox Elementary
301
14-Oct-11 02:09:43 PM
73.2
36.6
0.0
622
3
Issac Fox Elementary
302
14-Oct-11 12:15:54 PM
73.5
38.2
0.0
647
3
Issac Fox Elementary
303
14-Oct-11 11:42:02 AM
72.9
44.8
0.0
826
28
Issac Fox Elementary
305
14-Oct-11 02:11:10 PM
73.7
37.1
0.0
579
15
Issac Fox Elementary
307
14-Oct-11 02:12:21 PM
74.2
38.3
0.1
705
20
Issac Fox Elementary
308
14-Oct-11 11:40:13 AM
71.8
41.1
0.0
823
17
Issac Fox Elementary
309
14-Oct-11 11:38:49 AM
72.3
45.4
0.0
827
3
Issac Fox Elementary
310
14-Oct-11 11:37:30 AM
71.8
45.4
0.0
962
19
Issac Fox Elementary
311
14-Oct-11 11:36:32 AM
71.4
45.5
0.0
714
2
Issac Fox Elementary
312
14-Oct-11 11:35:13 AM
70.9
45.0
0.0
1008
23
Issac Fox Elementary
313
14-Oct-11 11:33:58 AM
70.3
48.7
0.0
876
14
Issac Fox Elementary
314
14-Oct-11 11:32:50 AM
69.0
41.1
0.1
660
9
Issac Fox Elementary
315
14-Oct-11 11:31:26 AM
70.1
49.9
0.0
950
21
Issac Fox Elementary
316
14-Oct-11 11:30:26 AM
69.3
49.2
0.2
896
19
Issac Fox Elementary
400A
14-Oct-11 12:33:01 PM
73.8
41.9
0.1
796
3
Issac Fox Elementary
401
14-Oct-11 02:04:48 PM
72.6
41.3
0.0
677
2
Issac Fox Elementary
402
14-Oct-11 12:35:01 PM
72.1
37.9
0.0
660
19
Issac Fox Elementary
403
14-Oct-11 12:37:47 PM
72.8
40.3
0.0
712
20
Issac Fox Elementary
404
14-Oct-11 02:06:03 PM
72.5
41.1
0.0
807
16
Site
Location
Issac Fox Elementary
Outdoor Air
Issac Fox Elementary
103
Issac Fox Elementary
Date/Time
Occupants
Taken by
Taken With
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Open
Window
Yes
Yes
Yes
Yes
Issac Fox Elementary
406
14-Oct-11 12:40:12 PM
71.8
36.9
0.2
689
19
Issac Fox Elementary
5
14-Oct-11 11:56:37 AM
74.5
36.5
0.0
625
2
Issac Fox Elementary
7
14-Oct-11 11:57:40 AM
74.9
37.6
0.0
639
1
Issac Fox Elementary
Café office
14-Oct-11 11:55:26 AM
74.8
37.6
0.0
641
7
Issac Fox Elementary
Gym 109
14-Oct-11 02:22:07 PM
72.8
35.1
0.0
618
26
Issac Fox Elementary
Nurse 102
14-Oct-11 11:54:14 AM
75.0
38.1
0.0
699
3
Issac Fox Elementary
100
14-Oct-11 11:53:04 AM
74.3
38.6
0.0
745
4
Principal office 14-Oct-11 02:18:37 PM
74.3
36.7
0.0
647
2
Issac Fox Elementary
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Denys
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Denys
Denys
Denys
Denys
Gray Wolf
Gray Wolf
Gray Wolf
Gray Wolf
Carbon Dioxido PPM
700+420=1120
Protocol: Readings taken after 10:30am
Issac Fox Elementary
Outdoor Air
17-Oct-11 01:18:03 PM
55.3
28.1
1.3
409
Issac Fox Elementary
405
17-Oct-11 01:25:26 PM
69.8
35.5
0.0
670
19
Issac Fox Elementary
9
17-Oct-11 01:21:31 PM
63.8
41.6
0.0
663
1
Issac Fox Elementary
201
17-Oct-11 01:22:58 PM
66.6
38.5
0.0
769
2
Carbon Dioxido PPM
700+409=1109
Protocol: Readings taken after 10:30am
Download